Fire hydrant requirements for new subdivisions
Read the official text at library.municode.com ↗New subdivisions must install fire hydrants, paid for by the developer, following spacing and water flow rules. The department decides where hydrants go and can adjust rules if the land use doesn't match the zoning. Some subdivisions near existing hydrants may not need new ones.
developers
The ordinance, as written (Maui County) — Fire protection
A copy, taken August 21, 2026. The version published by Maui County is the one that governs, and it may have changed since. Check it before relying on anything here.
A.
All subdivisions in any zoning district as described in title 19 of this code shall be required to install fire hydrants, which shall be paid for
by the subdivider and shall be in accordance with the requirements of this chapter.
In the event the proposed land use within the subdivision is inconsistent with the
permitted use as described in the zoning district, the department shall have the discretion
to adjust the requirements as set forth in this section.
B.
The spacing of fire hydrants along the streets shall be not more than two hundred
fifty feet apart in business, commercial, industrial, hotel and apartment districts,
not more than three hundred fifty feet apart in residential districts, and not more
than five hundred feet apart in rural and agricultural districts.
C.
The department shall determine the location of all fire hydrants. Unless otherwise
permitted by the department, all fire hydrants shall be located within the boundaries
of a subdivision. On dead end streets, unless otherwise permitted by the director,
the last fire hydrant shall be located no more than one-half the spacing distance
from the dead-end. Spacing of fire hydrants shall be measured along the public roadway.
D.
The department's standards for fire protection fire flow shall be the standards listed
in that certain publication kept on file with the department entitled "Insurance Services
Office's Guide for Determination of Required Fire Flows" issued by the Insurance Services
Office, 1974 edition, as may be amended from time to time, and incorporated herein
by reference. The minimum fire protection schedule shall be as follows:
FIRE PROTECTION SCHEDULE
MINIMUM FIRE FLOW REQUIREMENTS BY ZONING DISTRICT
ZONING DISTRICT
G.P.M.
HOURS
Agricultural
500
2
Rural
1,000
2
Residential
1,000
2
Duplex
1,250
2
A-1 Apartment
1,500
2
A-2 Apartment
2,000
2
Hotel
2,500
2
Business
2,000
2
Resort Commercial
2,000
2
Light Industrial
2,000
2
Heavy Industrial
2,500
2
Park
500
2
Airport
2,500
2
E.
Fire hydrants are not required for new subdivisions, which fall completely within
a radius of two hundred fifty feet from the nearest existing fire hydrant in business,
industrial, commercial, hotel, and apartment districts; three hundred fifty feet from
the nearest existing fire hydrant in residential districts; and five hundred feet
from the nearest existing fire hydrant in rural and agricultural districts. Where
any portion of a new subdivision is outside of such a radius, compliance with subsections
A through D of this section shall be required.
(Ord. No. 3730, § 1, 2010)