MCC §16.04E.400
Fire flow requirements for new land development
Read the official text at library.municode.com ↗New land development, including subdivisions and single parcels with four or more structures, must have a water supply that can deliver enough water to fight fires. The amount of water and how far apart fire hydrants must be depends on the type of land use. The fire official must approve the system design.
developershomebuyerslandowners
The ordinance, as written (Maui County) — Subsection 18.4.6 added
A copy, taken August 21, 2026. The version published by Maui County is the one that governs, and it may have changed since. Check it before relying on anything here.
Section 18.4 of the NFPA 1, as amended by the State Fire Code, is amended by adding
a new subsection to be designated subsection 18.4.6 to read as follows:
18.4.6 Fire flow requirements for land use development.
18.4.6.1 General. A water supply capable of delivering the required fire-flow must be provided for
all new land development including subdivisions and single parcel development intended
for four or more structures in accordance with subsection 18.4.6. The design of the
system will be subject to approval by the AHJ.
18.4.6.1.1 Fire flow, hydrant spacing, and dedicated water supply for fire protection must be
in accordance with the requirements for designated land use:
Agriculture, 500 gpm, and 500 feet spacing between hydrants.
Rural, 1,000 gpm, and 500 feet spacing between hydrants.
Single family, 1,000 gpm, and 350 feet spacing between hydrants.
Duplex, 1,250 gpm, and 350 feet between hydrants.
Townhouse and low-rise apartments, 1,500 gpm, and 250 feet spacing between hydrants.
Businesses, high rise apartments, and light industry, 2,000 gpm and 250 feet spacing
between hydrants.
Heavy industry and hotels, 2,500 gpm and 250 feet hydrant spacing.
18.4.6.2 The water supply must be provided by hydrants or other connections in accordance
with section 18.5 of this code, as approved by the AHJ.
18.4.6.2.1 Fire hydrants must be accessible to the fire department apparatus by roads meeting
the requirements of subsection 18.2.3.6 of this code.
18.4.6.2.2 On dead-end streets, the last fire hydrant must be located at one-half the spacing
distance from the dead-end. Spacing of fire hydrants must be measured along the roadway.
18.4.6.3 The duration for all required fire-flows must be two hours.
( Ord. No. 5754 , § 3, 2024)