MCC §16.25.405
Fire protection and design rules for Hawaiian-style structures
Read the official text at library.municode.com ↗This section sets fire safety rules and building design standards for Indigenous Hawaiian architecture structures (hale). It explains when fire sprinklers are needed, how they must be built, and the size and spacing rules for structural parts. It also requires smoke alarms in sleeping hale and water supply certification.
contractorshomeownerslandowners
The ordinance, as written (Maui County) — Fire protection; Design standards
A copy, taken August 21, 2026. The version published by Maui County is the one that governs, and it may have changed since. Check it before relying on anything here.
405.1 Fire protection classifications. Fire protection for Indigenous Hawaiʻian architecture structures shall be as required
in Table 405.1.
Table 405.1 — Fire Protection Requirements Based on Setback
Class
Setback Requirements
Fire
Protection
Requirements
A
The structure (or a group of structures) is:
1. Located at least 100 feet from any existing structure on the same or neighboring
properties; and
2. Located at least 100 feet from any property line, except as follows:
a. If the property line abuts a public way, the 100 feet minimum setback for that
property line shall be reduced by the width of the public way,
b. If the property line abuts the shoreline, the minimum setback for that property
line shall be the shoreline setback, or
c. For any hale ku'ai in the agricultural district that is less than 200 square feet,
that is completely open on three sides, and that is used as an agricultural products
stand and if the property line abuts a public way, the minimum setback for that property
line shall be 15 feet.
No fire protection is required for the structure.
B
The structure (or a group of structures) that conforms to applicable zoning setback
requirements but does not satisfy Class A setback requirements.
Automatic fire sprinkler system shall be installed in accordance with design standards
in section 3805.2. An electrical permit is required for fire sprinklers systems.
405.2 Automatic fire sprinklers. The design standards for automatic fire sprinklers for Class B indigenous Hawaiʻian
architecture structures shall be in accordance with NFPA 13.
Exception:
The design standards for automatic fire sprinklers for Class B indigenous Hawaiʻian
architecture structures shall be permitted as follows:
1. 18 gallons per minute for a single head at 140 square feet maximum coverage of
roof area.
2. 13 gallons per minute for each subsequent head at 140 square feet maximum coverage
of roof area per head.
3. The minimum supply pressure at the base of the riser shall not be less than 40
pounds per square inch.
4. The minimum residual pressure at the highest sprinkler shall be not less than 12
pounds per square inch.
5. Sprinkler head spacing shall not exceed 14 feet.
6. Sprinkler heads shall be open type upright, pendent, or sidewall with 1/2-inch
or 17/32-inch orifice and have a wax corrosion resistant coating.
7. The total number of sprinklers on a branch shall not exceed 6 heads.
8. The total number of sprinklers shall not exceed the quantity shown in Table 405.2(a).
Table 405.2(a) — Total Number of Fire Sprinklers Based on Pipe Size
Pipe Sizing
Number of Sprinklers
1 inch diameter
2 sprinklers
1 ¼ inch diameter
3 sprinklers
1 ½ inch diameter
5 sprinklers
2 inch diameter
10 sprinklers
2 ½ inch diameter
30 sprinklers
3 inch diameter
60 sprinklers
9. The pipe schedule in Table 405.2(a) shall not apply to hydraulically designed systems.
10. The water density shall not be less than 0.10 gpm per square foot.
11. The source of water may be by domestic water meters, detector check meter, underground
well, storage tank, swimming pool, ponds, etc., but must meet the design requirements
for adequate pressure and duration.
12. Water supply shall be sufficient to provide 30 minutes duration.
13. If domestic water meters are used as the source of water for the fire sprinklers,
without a storage tank and booster pump, the maximum number of sprinklers shall not
exceed the number shown in Table 405.2(b).
Table 405.2(b) — Total Number of Fire Sprinklers Based on Water Meter Size
Size of Water Meter
Number of Sprinklers
⅝ inch water meter
1 sprinkler
¾ inch water meter
2 sprinklers
1 inch water meter
3 sprinklers
1 ½ inch water meter
7 sprinklers
2 inch water meter
11 sprinklers
3 inch water meter
27 sprinklers
14. The piping material shall be hard drawn copper with silver solder or brazed fittings,
or carbon steel with corrosion-resistant coatings. Plastic pipes shall not be allowed,
except for below grade supply pipes.
15. Fire sprinkler system shall be actuated by smoke detectors located at the highest
points of the roof and spaced as recommended by the manufacturer.
16. Flow control valves shall be either hydraulically or electrically operated with
a manual override switch.
17. Where the width of a roof exceeds the width allowed for one row of sprinklers,
two or more rows of sprinklers shall be placed such that the entire roof area is protected.
18. Prevailing wind direction shall be considered in the placement of sprinklers.
19. Deflectors for sprinklers shall be parallel with the roof surface or tilted slightly
towards the peak of the roof.
20. Fire sprinklers system shall have a local alarm activated by a smoke detector.
405.3 Certification of water supply. For any hale that requires fire protection pursuant to section 405, the applicant
shall provide a certification from a licensed engineer or a licensed C-20 contractor
that the water supply for the fire sprinkler system has been tested and is capable
of delivering the required fire flow for 30 minutes duration.
405.4 Smoke alarm. Any hale used for sleeping shall have an approved battery-operated smoke alarm installed
in the hale.
( Ord. No. 5507 , § 2, 2023)
SECTION 406 DESIGN STANDARDS
406.1 General design standards. All types of hale shall be designed and constructed in accordance with the standards
set out in this section.
1. The minimum diameter size of all structural members shall be measured at the member's
midpoint, except that the minimum diameter size of posts shall be measured at the
smaller end. For structure sizes not specifically shown in the tables, the requirements
in the next larger width size shall be applicable.
2. The specifications for structural members were estimated based on no wind loads.
Hale shall be constructed to allow all thatching materials to separate from the structure
prior to adding significant loads.
3. The mix formula for mortar specified in these rules shall be one part portland
cement, four parts clean sand, and sufficient fresh water to make the mixture workable.
4. Every hale, except hale noa, shall have at least two sides completely open.
5. Lashing and thatching methods shall comply with illustrations found in "Arts and
Crafts of Hawaiʻi" or "The Hawaiʻian Grass House in Bishop Museum" referenced in section
401.2.
406.2 Allowable designs. Hale shall be designed and constructed in accordance with the requirements in sections
406.2.1 through 406.2.4.
406.2.1 Hale Hālāwai. Each end of the Hale Hālāwai may be open or thatched. The ends may also be constructed
with a thatched roof hip as an alternate design. Hale Hālāwai shall be designed in
accordance with the following schematics and illustrations. Structural components
for Hale Hālāwai shall meet the size and spacing requirements in Table 406.2.1(a).
Foundations for Hale Hālāwai shall be designed in accordance with Table 406.2.1(b).
HALE HĀLĀWAI
Open End Style
HALE HĀLĀWAI
Thatched End Style
Framing Schematic
Table 406.2.1(a) — Size and Spacing Requirements for Structural Components used in
Hale Hālāwai
Size
W × L × H
pou
kihi
pou kukuna &
pou kaha
pou hana &
pouo manu
o'a
kuaiole &
holo
kauhuhu
lohelau
Maximum
post
spacing
(feet)
Maximum
rafter
spacing
(feet)
Minimum Diameter (inches)
12′ × 20′ × 7′
4
3 ½
4
3 ½
2 ½
3
3
5
3
14′ × 24′ × 7′
4
4
4 ½
3 ½
2 ½
3
3 ½
5
3
24′ × 30′ × 7′
5
4 ½
4 ½
4
2 ½
3
3 ½
5
3
25′ × 50′ × 7′
5 ½
5
5 ½
4
2 ½
3
3 ½
5
3
30′ × 60′ × 7′
6
5 ½
6
4 ½
2 ½
3
4
5
3
KAHUA
(PEDESTAL)
PĀ PŌHAKU (FOUNDATION WALL)
POU KANU
(BURIED POST)
Table 406.2.1(b) — Foundation Design for Hale Hālāwai
Size
W × L × H
Foundation Type
kahua
Diameter ×
Height
pā pōhaku
Width × Height × Length
pou kanu
Diameter ×
Depth
12′ × 20′ × 7′
3′6″φ × 24″H
2′6″W × 2′8″H × 4′0″L
30″φ × 2′8″D
14′ × 24′ × 7′
3′8″φ × 24″H
2′6″W × 2′8″H × 4′0″L
30″φ × 2′9″D
24′ × 30′ × 7′
4′0″φ × 30″H
3′0″W × 3′0″H × 4′0″L
36″φ × 3′0″D
25′ × 50′ × 7′
4′0″φ × 30″H
3′0″W × 3′0″H × 4′0″L
36″φ × 3′0″D
30′ × 60′ × 7′
4′0″φ × 30″H
3′0″W × 3′3″H × 4′0″L
36″φ × 3′3″D
406.2.2 Hale Kuʻai. Hale Kuʻai shall be designed in accordance with the following schematics and illustrations.
Structural components for Hale Kuʻai shall meet the size and spacing requirements
in Table 406.2.2(a). Foundations for Hale Kuʻai shall be designed in accordance with
Table 406.2.2(b).
HALE KUʻAI
SHED STYLE
HALE KUʻAI
GABLE STYLE
FRAMING SCHEMATIC 1
FRAMING SCHEMATIC 2
Table 406.2.2(a) — Size and Spacing Requirements for Structural Components used in
Hale Kuʻai
Size
(W × L × H)
pou
kihi a
pou
kaha a
pou
hana b
pouo
manu b
o'a
kuaiole
& holo
kauhuhu
lohelau
Maximum
rafter
spacing
(feet)
Minimum Diameter (inches)
5′ × 10′ × 5′
4
3
3
4
3
2
3
2
4
9′ × 12′ × 5′
4
3
3
4
3
2
3 ½
2
4
12′ × 16′ × 5′
4 ½
3 ½
4
4
3 ½
2
4
2 ½
4
14′ × 20′ × 5′
4 ½
3 ½
4
4
3 ½
2 ½
4 ½
2 ½
4
a
The maximum post spacing for pou kihi and pou kaha is five feet.
b
The maximum post spacing for pou hana and pouomanu is twelve feet.
KAHUA
(PEDESTAL)
POU KANU
(BURIED POST)
Table 406.2.2(b) — Foundation Design for Hale Kuʻai
Size
(W × L × H)
Foundation Type
kahua
Diameter × Height
pā pōhaku
Width × Height × Length
pou kanu
Diameter × Depth
5′ × 10′ × 5′
3′0″φ × 24″H
2′6″W × 2′0″H ×4′0″L
30″φ × 2′6″D
9′ × 12′ × 5′
3′4″φ × 24″H
2′6″W × 2′0″H × 4′0″L
30″φ × 2′6″D
12′ × 16′ × 5′
3′6″φ × 24″H
2′6″W × 2′8″H × 4′0″L
30″φ × 2′8″D
14′ × 20′ × 5′
3′8″φ × 24″H
2′6″W × 2′8″H × 4′0″L
30″φ × 2′9″D
406.2.3 Hale Noa. Hale Noa shall have at least two openings. One opening shall be at least 3 feet wide
and 5 feet high, and the other opening shall be at least 2 feet wide and 3 feet high.
Hale Noa shall be designed in accordance with the following schematics and illustrations.
Structural components for Hale Noa shall meet the size and spacing requirements in
Table 406.2.3(a). Foundations for Hale Noa shall be designed in accordance with Figure
406.2.3(b).
HALE NOA
FRAMING SCHEMATIC
Table 406.2.3(a) — Size and Spacing Requirements for Structural Components used in
Hale Noa
Size
(W × L × H)
pou
kihi
pou
kukuna
& pou
kaha
pou
hana
pouo
manu
o'a
kuaʻiole
&
holo
kauhuhu
lohelau
Maximum
post
spacing
(feet)
Maximum
rafter
spacing
(feet)
Minimum Diameter (inches)
9′ × 12′ × 7′
3 ½
3
4
3
3
2 ½
3 ½
2 ½
6
4
12′ × 20′ × 7′
4
4 ½
4
3
3 ½
2 ½
3 ½
2 ½
6
4
4′ × 24′ × 7′
5 ½
4 ½
4
3
3 ½
2 ½
3 ½
3
6
4
Figure 406.2.3(b)
406.2.4 Hale Waʻa. Hale Waʻa shall be designed in accordance with the following schematics and illustrations.
Structural components for Hale Waʻa shall meet the size and spacing requirements in
Table 406.2.4(a). Foundations for Hale Waʻa shall be designed in accordance with Figure
406.2.4(b).
HALE WAʻA
FRAMING SCHEMATIC
Table 406.2.4(a) - Size and Spacing Requirements for Structural Components used in
Hale Waʻa
Size
(W × L)
oʻa
kuaʻiole
& holo
kauhuhu
Spacing
between
Rafters
Minimum
ridge
Height (H)
20′ × 60′
4″
3″
4″
4′ to 5′
22½′
25′ × 60′
5″
3″
4″
4′ to 5′
27½′
30′ × 60′
5½″
3″
4″
4′ to 5′
27½′
Figure 406.2.4(b)
( Ord. No. 5507 , § 2, 2023)
_____
Read the official text at library.municode.com ↗as published Nov 21, 2025our copy taken Aug 21, 2026
Published by the County of Maui through Municode.
LawTrove is not legal advice. The summary above is a computer-generated restatement — the authoritative text is the official version linked above.